range of product |
Altivar Easy 610
|
|
---|---|---|
product or component type |
Variable speed drive
|
|
product specific application |
Fan, pump, compressor, conveyor
|
|
device short name |
ATV610
|
|
variant |
Standard version
|
|
product destination |
Asynchronous motors
|
|
mounting mode |
Cabinet mount
|
|
EMC filter |
Integrated conforming to EN/IEC 61800-3 category C3 with 50 m maximum
|
|
IP degree of protection |
IP20
|
|
type of cooling |
Forced convection
|
|
supply frequency |
50...60 Hz (+/-5 %)
|
|
network number of phases |
3 phases
|
|
[Us] rated supply voltage |
380...415 V (- 15...10 %)
|
|
motor power kW |
45 kW normal duty
37 kW heavy duty |
|
motor power hp |
60 hp normal duty
50 hp heavy duty |
|
line current |
92.9 A at 380 V normal duty
88.3 A at 415 V normal duty 80.5 A at 380 V heavy duty 75.8 A at 415 V heavy duty |
|
prospective line Isc |
22 kA
|
|
apparent power |
63.5 kVA at 415 V normal duty
54.5 kVA at 415 V heavy duty |
|
continuous output current |
88 A at 4 kHz normal duty
75 A at 4 kHz heavy duty |
|
maximum transient current |
97 A during 60 s normal duty
112 A during 60 s heavy duty |
|
asynchronous motor control profile |
Constant torque standard
Variable torque standard Optimized torque mode |
|
output frequency |
0.0001...0.5 kHz
|
|
nominal switching frequency |
4 kHz
|
|
switching frequency |
2...12 kHz adjustable
|
|
number of preset speeds |
16 preset speeds
|
|
communication port protocol |
Modbus serial
|
|
option card |
Slot A : communication card Profibus DP V1
Slot A : digital or analog I/O extension card Slot A : relay output card |
output voltage |
<= power supply voltage
|
|
---|---|---|
motor slip compensation |
Adjustable
Automatic whatever the load Can be suppressed Not available in permanent magnet motor law |
|
acceleration and deceleration ramps |
Linear adjustable separately from 0.01 to 9000 s
S, U or customized |
|
braking to standstill |
By DC injection
|
|
protection type |
Motor : thermal protection
Motor : motor phase break Drive : thermal protection Drive : overheating Drive : overcurrent between output phases and earth Drive : overload of output voltage Drive : short-circuit protection Drive : motor phase break Drive : overvoltages on the DC bus Drive : line supply overvoltage Drive : line supply undervoltage Drive : line supply phase loss Drive : overspeed Drive : break on the control circuit |
|
frequency resolution |
Display unit : 0.1 Hz
Analog input : 0.012/50 Hz |
|
electrical connection |
Line side, screw terminal : 35...50 mm²
Control, screw terminal : 0.5...1.5 mm² Motor, screw terminal : 50 mm² |
|
connector type |
1 RJ45 (on the remote graphic terminal) for Modbus serial
|
|
physical interface |
2-wire RS 485 for Modbus serial
|
|
transmission frame |
RTU for Modbus serial
|
|
transmission rate |
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
|
|
type of polarization |
No impedance for Modbus serial
|
|
number of addresses |
1...247 for Modbus serial
|
|
method of access |
Slave
|
|
supply |
External supply for digital inputs : 24 V DC (limits : 19...30 V), <= 1.25 mA (overload and short-circuit protection)
Internal supply for reference potentiometer (1 to 10 kOhm) : 10.5 V DC +/- 5 %, <= 10 mA (overload and short-circuit protection) |
|
local signalling |
1 LED red for presence of voltage
2 LEDs for local diagnostic 1 LED yellow for embedded communication status 2 LEDs dual colour for communication module status |
|
width |
226 mm
|
|
height |
613 mm
706 mm with EMC plate |
|
depth |
271 mm
|
|
product weight |
26.8 kg
|
|
analogue input number |
3
|
|
analogue input type |
Software-configurable voltage AI1, AI2, AI3 : 0...10 V DC, impedance 30 kOhm, resolution 12 bits
Software-configurable current AI1, AI2, AI3 : 0...20 mA, impedance 250 Ohm, resolution 12 bits Software-configurable temperature probe or water level sensor AI2, AI3 |
|
discrete input number |
6
|
|
discrete input type |
Programmable as pulse input DI5, DI6 0...30 kHz : 24 V DC (limits : <= 30 V)
Programmable as logic input DI1...DI6 : 24 V DC (limits : <= 30 V), impedance 3.5 kOhm |
|
input compatibility |
Level 1 PLC conforming to EN/IEC 61131-2, logic input DI1...DI6
Level 1 PLC conforming to IEC 65A-68, pulse input DI5, DI6 |
|
discrete input logic |
Positive logic (source) : DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) : DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source) : DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1) |
|
analogue output number |
2
|
|
analogue output type |
Software-configurable current AQ1, AQ2 : 0...20 mA, resolution 10 bits
Software-configurable voltage AQ1, AQ2 : 0...10 V DC,impedance 470 Ohm, resolution 10 bits |
|
sampling duration |
Analog input AI1, AI2, AI3 : 5 ms (+/- 0.1 ms)
Analog output AQ1, AQ2 : 10 ms (+/- 1 ms) Discrete input DI1...DI6 : 2 ms (+/- 0.5 ms) configurable Pulse input DI5, DI6 : 5 ms (+/- 1 ms) configurable |
|
accuracy |
Analog input AI1, AI2, AI3 : +/- 0.6 % for a temperature variation 60 °C
Analog output AQ1, AQ2 : +/- 1 % for a temperature variation 60 °C |
|
linearity error |
Analog input AI1, AI2, AI3 : +/- 0.15 % of maximum value
Analog output AQ1, AQ2 : +/- 0.2 % |
|
relay output number |
3
|
|
relay output type |
Configurable relay logic R1 : fault relay NO/NC, electrical durability 100000 cycles
Configurable relay logic R2 : sequence relay NO, electrical durability 100000 cycles Configurable relay logic R3 : sequence relay NO, electrical durability 100000 cycles |
|
refresh time |
Relay output R1, R2, R3 : 5 ms (+/- 0.5 ms)
|
|
minimum switching current |
Relay output R1, R2, R3 : 5 mA at 24 V DC
|
|
maximum switching current |
Relay output R1, R2, R3 on resistive load (cos phi = 1 : 3 A at 250 V AC
Relay output R1, R2, R3 on resistive load (cos phi = 1 : 3 A at 30 V DC Relay output R1, R2, R3 on inductive load (cos phi = 0.4 and L/R = 7 ms) : 2 A at 250 V AC Relay output R1, R2, R3 on inductive load (cos phi = 0.4 and L/R = 7 ms) : 2 A at 30 V DC |
|
isolation |
Between power and control terminals
|
|
insulation resistance |
> 1 mOhm at 500 V DC for 1 minute to earth
|
noise level |
75 dB conforming to 86/188/EEC
|
|
---|---|---|
power dissipation in W |
1000 W (forced convection) at 380 V, switching frequency 4 kHz
121 W (natural convection) at 380 V, switching frequency 4 kHz |
|
volume of cooling air |
240 m3/h
|
|
operating position |
Vertical +/- 10 degree
|
|
electromagnetic compatibility |
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
|
pollution degree |
2 conforming to EN/IEC 61800-5-1
|
|
vibration resistance |
1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6 |
|
shock resistance |
15 gn during 11 ms conforming to IEC 60068-2-27
|
|
relative humidity |
5...95 % without condensation conforming to IEC 60068-2-3
|
|
ambient air temperature for operation |
-15...45 °C without derating
45...60 °C with derating factor |
|
ambient air temperature for storage |
-40...70 °C
|
|
operating altitude |
1000...4800 m with current derating 1 % per 100 m
<= 1000 m without derating |
|
environmental characteristic |
Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3
Dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3 |
|
standards |
EN/IEC 61800-3
EN/IEC 61800-3 environment 2 category C3 EN/IEC 61800-5-1 IEC 60721-3 |
|
product certifications |
REACH
|
|
marking |
CE
|
Sustainable offer status |
Green Premium product
|
|
---|---|---|
RoHS (date code: YYWW) | ||
REACh | ||
Product environmental profile | ||
Product end of life instructions |